The applications of temperature control are very common both in processes and in utilities for the industry. They usually are zones of high energy consumption and many hours of operation. This means that it is convenient to take into account a good selection and regulation of the pumps installed in these circuits. Regarding the type of regulation we present 3 ways to do it:
System regulation
The diagram shown below presents three examples, all with the same system requirement: a specific temperature of a heat exchanger. However, the way to achieve the goal is very different. The difference in philosophy lies in what we call the development from S to E to I (from the Standard product approach to the Electronic product approach and the Intelligent system approach, such as GRUNDFOS iSolutions concept).
S: This system operates at constant speed (Fig. 1): that is, the pump rotates at a constant speed. We measure the temperature at the point of discharge of the heat exchanger, which feeds a regulating valve, and regulates the temperature by reducing the flow that passes through the heat exchanger. The result for the pump will be that it slides up and down the curve of the pump. (The red curve of the pump in Fig. 4.)
E: The second system (Fig. 2) is very common in many applications. Here we have a pump that is regulated at a constant differential pressure, that is, it maintains a constant differential pressure between the discharge of the pump and the return of the heat exchanger. But, again, the heat exchanger outlet temperature is controlled as in configuration 1, where we have a temperature-controlled regulating valve that limits the flow to be able to have a constant temperature.
The result for the pump will be that it maintains a constant pressure, a horizontal curve in the Q / h chart. (The yellow curve of the pump in Fig. 4.)
I: The last example is the "I" system: the "Intelligent" way of doing things (fig.3). We measure the temperature and send the signal directly to the E motor (a
motor with integrated frequency converter). In addition, we use the PI regulator of the E motor to maintain a flow rate, which corresponds to the temperature
desired heat exchanger. We no longer need the regulating valve and, therefore, we eliminate the loss of continuous pressure that it generates.
The result for the pump will be that it follows a curve very similar to the proportional pressure. (The green curve of the pump in Fig. 4.)
In the curve diagram of Figure 4 we can see a comparison of the three systems in which different load curves appear. The reason why system I (direct temperature control) shows a flat flow with low loads is because we want to maintain a small flow in the system to supply the information obtained to the temperature transmitter.
When a heating and cooling system is available, it is not possible to stop the pumps completely; There must be a minimum flow to have something to measure.
These three different curves are related to each system. Remember, all three systems do the same work: provide a constant temperature outside the
heat exchanger.
If we observe the energy consumption of each system, we can see the energy consumption for the load curve at maximum speed, the differential load curve at constant pressure and the load curve at direct temperature. If we observe each system operating at one third of its load, we can see that there is a huge difference in energy consumption, which can be directly related to energy savings. On the other hand, there are few differences between the systems when they operate at full flow capacity, since the chosen regulation method no longer plays any role. However, it is necessary to ensure that the pump has been sized correctly for the task.