What is predictive maintenance for industrial motors?

Predictive maintenance is a maintenance strategy based on monitoring the actual condition of equipment through non-destructive measurement techniques. Its aim is to detect incipient deterioration of an electric motor before it becomes a failure, allowing intervention to be planned at the optimal time.

Steknos offers an on-site predictive maintenance service designed specifically for industrial electric motors. We visit the customer's facility with high-precision portable equipment and carry out a full diagnosis —mechanical, electrical or comprehensive— with minimal impact on production.

Mechanical predictive inspection: diagnosis without stopping the machine

The mechanical predictive inspection is aimed at the maintenance manager who needs to know the mechanical condition of their motors without stopping production. All equipment used is portable and does not require electrical disconnection or machine shutdown, so the operational impact is virtually nil.

With this inspection, the customer obtains objective, quantified information on bearing condition, the presence of misalignment between motor and driven machine, balancing of the rotating assembly, lubrication quality and the general condition of the baseplate and anchorages.

Mantenimiento predictivo de motores eléctricos Steknos · medición de aislamiento con megger industrial · análisis de resistencia IR e índice de polarización PI · diagnóstico eléctrico en planta para anticipar fallo de bobinado

Vibration analysis and FFT spectrum

Vibration analysis is the core technique of mechanical predictive maintenance. Using triaxial accelerometers installed at standardised measurement points (according to ISO 10816 and ISO 20816), we record the motor's vibration signals while in operation and process them by FFT (Fast Fourier Transform) spectral analysis.

The vibration spectrum is, in essence, the "fingerprint" of the motor's mechanical condition. Each type of defect generates a characteristic frequency pattern that allows precise identification of:

  • Rotor unbalance
  • Motor-machine misalignment
  • Bearing deterioration
  • Mechanical looseness
  • Gear defects
Técnico realizando medición de vibraciones en bomba industrial con analizador portátil durante mantenimiento predictivo en instalación industrial

Temperature monitoring and infrared thermography

Temperature monitoring of the motor and driven machine complements vibration analysis. An abnormal temperature rise may indicate overload, ventilation problems, insulation failure or bearing deterioration.

We use two complementary techniques:

  • 1. Contact/infrared pyrometer: spot temperature measurement on housing, end shield covers, bearings and connections. Fast and direct.
  • 2. Infrared thermography: using a thermal imaging camera, we obtain a complete thermal image of the motor surface and its surroundings, enabling detection of asymmetric hot spots, ventilation problems and electrical connections with high contact resistance.

Baseplate inspection and lubrication check

To complete the mechanical inspection, our technicians carry out a visual and dimensional inspection of the motor mounting baseplate, verifying:

  • Condition of anchor bolts and tightening torque.
  • Condition of feet and alignment shims.
  • Condition of the coupling (flexible, rigid, chain, belt): wear, clearances and alignment.

Electrical predictive inspection: actual condition of winding and circuit

The electrical predictive inspection requires stopping the machine and disconnecting the motor terminals to connect the analysis equipment. In return, it provides electrical condition information that cannot be obtained in any other way with the motor installed in place.

With this inspection, the customer learns the actual condition of the winding insulation, phase symmetry, winding resistance and —for DC motors— brush and commutator condition.

Motor eléctrico industrial certificado ATEX reacondicionado en taller especializado para uso en zonas con atmósferas explosivas

ACCURATE DIAGNOSIS WITHOUT STOPPING YOUR PRODUCTION

We carry out vibration analysis and thermography with the motor running. Detect bearing faults or misalignment without disconnecting equipment or losing a minute of operation.

Insulation measurement and polarisation index (Megger)

Insulation measurement using a megohmmeter (Megger) is the most fundamental electrical predictive test. It applies a controlled DC voltage (500 V, 1,000 V or 2,500 V depending on the motor's rated voltage) and measures the insulation resistance between the windings and the motor frame.

The values obtained allow evaluation of:

  • Insulation resistance (IR): spot value indicating whether insulation is in good condition, degraded or at risk of failure. Minimum acceptable values are set according to IEEE 43.
  • Polarisation index (PI): ratio of insulation resistance measured at 10 minutes to that at 1 minute. A PI above 2.0 indicates healthy insulation; values below 1.5 indicate contamination by moisture, conductive dust or varnish degradation. It is a more reliable indicator than the spot IR value because it removes the influence of ambient temperature.
  • Dielectric absorption ratio (DAR): ratio of IR at 60 s to that at 30 s, providing complementary information on the degradation mechanism.
Diagnóstico de motor eléctrico industrial con bobinado dañado en taller especializado · inspección de conexiones en caja de bornes y evaluación del estado del estator · reparación de motores eléctricos y análisis de fallos por sobrecalentamiento realizada por Steknos
Mantenimiento predictivo de motores eléctricos Steknos · prueba Surge y análisis de aislamiento con equipo Megger ADX4 · comparación de fases y detección de cortocircuitos entre espiras · diagnóstico eléctrico avanzado en planta industrial

Phase comparison and Surge test

The phase comparison test (Surge test) is a specific test to detect insulation defects between turns within the same winding, a type of fault that the megger cannot identify because the test voltage is not applied between adjacent turns.

The Surge equipment applies high-voltage pulses to each phase of the motor and compares the resulting waveforms. In a healthy motor, the three phases produce virtually identical waveforms. Any asymmetry indicates an inter-turn short circuit, an inductance difference or incipient insulation defect.

This test is especially valuable for motors operating with variable frequency drives, as the inverter's PWM pulses subject the winding insulation to dielectric stress far greater than direct mains supply.

In addition, we carry out DC phase resistance measurement, which detects phase imbalances caused by shorted turns, poor connections or conductor cross-section differences.

Informe de mantenimiento predictivo de motores eléctricos Steknos · análisis de datos de vibraciones, aislamiento y termografía en oficina técnica · elaboración de diagnóstico y planificación de intervención basada en estado real del equipo

Predictive vs. preventive maintenance: differences and when to choose each

It is one of the questions we most often receive from plant managers. Both strategies are complementary, not mutually exclusive; but understanding their differences helps optimise the maintenance budget.

When to choose predictive maintenance? The practical rule we apply at Steknos is to evaluate the "cost of consequence": if the unplanned failure of a motor paralyses a production line whose downtime cost exceeds €500–1,000/hour, predictive pays for itself with the first failure avoided. For auxiliary or low-impact motors, calendar-based preventive maintenance remains a reasonable and more economical option to manage.

The most efficient combination for an industrial plant is to apply predictive maintenance to critical motors (typically 15–20% of the fleet, which accounts for 80% of downtime risk) and maintain a standard preventive plan for the rest.

Industrial sectors and applications

Steknos's on-site predictive maintenance service serves factories and industrial plants across all productive sectors:

  • Automotive and metalworking: press lines, robots, conveyors, compressors and ventilation systems. Critical motors with high downtime cost.
  • Food and beverage industry: packaging line motors, cold rooms, process and ventilation pumps. Environments with moisture and dust that accelerate insulation degradation.
  • Chemical and pharmaceutical: reactor, agitator, transfer pump and centrifuge motors. High criticality for process safety.
  • Water and sanitation: pumping, blower and treatment station motors. Continuous operation with limited access for maintenance.
  • Logistics and intralogistics: automated transport system, sorter and elevator motors. High volume of equipment with medium-high criticality.
  • Energy and utilities: large fan, pump and compressor motors in power plants and substations.
Mantenimiento predictivo de motor y bomba industrial Steknos · verificación de alineación y estado del acoplamiento elástico · diagnóstico mediante análisis de vibraciones para prevenir desalineaciones y desgaste prematuro · inspección mecánica en planta

Frequently asked questions about predictive maintenance

What is predictive maintenance and how does it differ from preventive?

Predictive maintenance bases intervention decisions on the actual condition of the equipment, measured through techniques such as vibration analysis, insulation measurement or thermography. Preventive maintenance, by contrast, schedules inspections by calendar or operating hours, regardless of motor condition. The practical difference is that predictive intervenes only when there is evidence of deterioration, avoiding both unnecessary shutdowns and unplanned failures.

How much does a vibration analysis service cost?

The cost depends on the number of motors to be inspected, the type of inspection (mechanical, electrical or comprehensive) and the frequency. Steknos offers fixed quotes tailored to each plant. As a guide, an annual predictive programme for a fleet of 20 critical motors has a cost that pays for itself with the first unplanned failure avoided.

Is it necessary to stop production to carry out predictive maintenance?

Not always. The mechanical predictive inspection (vibration analysis, thermography, lubrication check) is carried out with the motor running, without needing to stop the machine. Only the electrical inspection requires disconnecting the motor to connect the measurement equipment (megger, surge test). That is why many customers start with the mechanical inspection and schedule the electrical one during already planned shutdowns.

How is a bearing fault detected before it fails?

Through vibration analysis in the high-frequency band. Each bearing defect (outer race, inner race, rolling elements, cage) generates a characteristic vibration frequency that can be calculated from the bearing geometry. These frequencies appear in the spectrum weeks or months before the deterioration is audible or causes a temperature rise. This is the window of opportunity that allows the bearing change to be planned without an unplanned shutdown.

My motor vibrates a lot: is it serious?

It depends on the level and pattern of vibration. ISO 10816 classifies vibration severity in four zones (A, B, C, D). A motor in zone C requires monitoring and intervention planning; a motor in zone D needs immediate shutdown to avoid catastrophic damage. Diagnosis of the vibration pattern (FFT spectrum) determines the cause: unbalance, misalignment, bearing, looseness or others.

How often should predictive maintenance be carried out?

The optimum frequency depends on motor criticality and the operating environment. As a general reference, for critical motors quarterly mechanical and semi-annual electrical inspections are recommended. For medium-criticality motors, semi-annual and annual respectively. Steknos adapts the frequency to each equipment's risk profile.

What is the polarisation index and what is it for?

The polarisation index (PI) is the ratio of insulation resistance measured at 10 minutes to that measured at 1 minute of DC voltage application. Values above 2.0 indicate clean, dry insulation; values below 1.5 indicate contamination (moisture, conductive dust) or insulating varnish degradation. It is a more reliable indicator than the spot resistance value because it is independent of ambient temperature.

What is the Surge test and what is it for?

The Surge test applies voltage pulses to each phase of the motor and compares the resulting waveforms. It detects inter-turn short circuits and insulation defects within the winding itself, which are faults that the megger cannot identify. It is especially important in motors supplied by variable frequency drives, where dielectric stress on the winding is much higher than with direct mains supply.